Conduit fill calculator
Wires in, smallest conduit out.
How it is worked out
Add up the cross-section area of every wire, insulation included. The conduit is big enough when that total is no more than the fill the code allows: 53% of the conduit's area for one wire, 31% for two, 40% for more than two. Example: four #6 THHN (0.0507 square inches each) and two #8 THHN (0.0366 each) add up to 0.276 square inches. 3/4 inch EMT allows 0.213, so it is too small; 1 inch EMT allows 0.346, so 1 inch is the answer.
Areas are the NEC chapter 9 table values for THHN/THWN and TW/THW building wire. Check the code edition your jurisdiction has adopted, and remember that more than three current-carrying conductors in one conduit means derating their ampacity.
Bending the conduit
Try the offset calculator and the 3-point saddle calculator. Bend Calc for iPhone and iPad has conduit fill and every common bend in one place, free for the basics, with no ads and no subscription.
Benders differ. Check the take-up on yours and make a test bend before you cut. No more than 360° of bends between pull points.